BKBLJ - EXTINGUISHER,FIRE,VAPORIZING LIQUID

Product Identification

Product ID:EXTINGUISHER,FIRE,VAPORIZING LIQUID
MSDS Date:07/12/1989
FSC:4210
NIIN:00-708-0031
MSDS Number: BKBLJ

Responsible Party
GENERAL FIRE EXTINGUISHER CORP.
1685 SHERMER ROAD
NORTHBROOK, IL 60062-5315
US

Emergency Phone: 312-272-7500

Info Phone: 312-272-7500

Preparer: DGSC-SLM/ DOD-HMIS

Cage: 99539

Contractor
GENERAL FIRE EXTINGUISHER CORP
NORTHBROOK, IL 60062-5315 US

Telephone: (708) 847-272-7500; 847-272-7500

Cage: 99539

Ingredients

BROMOCHLORODIFLUOROMETHANE (AS EXTINGUISHING AGENT)

CAS: 353-59-3

RTECS: PA5270000

OSHA PEL NONE ESTABLISHED

ACGIH TLV: NONE ESTABLISHED


NITROGEN

CAS: 7727-37-9

RTECS: QW9700000

ACGIH TLV: ASPHYXIANT; 9192

Hazards

LD50 LC50 Mixture:LC50 (RAT): 20 PPH/15M
Routes of Entry: Inhalation:YES Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:ACUTE: ASPHYXIANT 'CNS' & PULMONARY
EFFECTS. SKIN IRRITANT, CHRONIC: NONE KNOWN.
Effects of Overexposure:INHAL: DIZZINESS, DISORIENTATION, IMPAIRE
COORDINATION, NARCOSIS, NAUSEA, OR VOMITING, LIGHT-HEADEDNESS
GIDDINESS, BREAT SHORTNESS. CARDIAC ARRHYTHMIA W/ UNCONSCIOUSNESS
OR EVEN DEATH IN HI-CONC W/LO EXPOSURES; SKIN/EYES: CONTACT
W/LIQUUIDCAN CAUSE FROSTBITE, OR SKIN IRRITATION.
Medical Cond Aggravated by Exposure:CARDIAC PROBLEMS. (PRODUCT IS AN

First Aid

First Aid:INHAL: REMOVE TO FRESH AIR-GET MED. ATTN.GIVE O*2/CPR AS
REQUIRED FOR SITUATION & @ HAND; DONOT GIVE EPINEPHRINE OR SIMILIAR
DRUGS AS CATECOLAMINES INCREASE RISK OF ELICITING CARDIAC
DYSRYTHMIAS EYES/ SKIN: FLUSH CARDIAC DYSRYTHMIAS. FROSTBITE W/
MEDICALATTN. ; INGEST: NOT LIKELY TO OCCUR.

Fire Fighting

Flash Point:NONE
Extinguishing Media:MATERIAL IS A FIRE EXTINGUISHANT & IS
NON-FLAMMABLE. USE MEDIA APPROPRIATE FOR SURROUNDING FIRE.
Fire Fighting Procedures:USE 'SCBA' WHEN FIGHTING FIRES WHERE CHEMICALS
ARE INVOLVED. 'SCBA' MAY BE NEEDED IF HALON-1211 CONTAINER RUPTURES
RELEASES MATERIAL IN HEAT OF FIRE.
Unusual Fire/Explosion Hazard:IN HEAT OF FIRE, HALON-1211 CONTAINER
EXPOSED TO INTENSE HEAT OF FIRE MAY RUPTURE & MATERIAL COMPOSITION
MAY OCCUR.

Accidental Release

Spill Release Procedures:EVACUATE AREA OF UNNEDED PERSONNEL,VENTILATE
AREA ESPECIALLY LOW PLACES WHERE HEAVY VAPORS MIGHT COLLECT. COOL
OR REMOVE HOT METAL SURFACES OR SOURCES OF NON-EXTINGUISHED FLAMES.

Handling

Handling and Storage Precautions:STORE & HANDLE AS A LIQUIFIE
COMPRESSED GAS IN 'DOT' APPROVED PRESSURE VESSELS AWAY FROM
HI-TEMPERATURES.
Other Precautions:AVOID UNNECESSARY EXPOSURE TO HALON 1211 ! ABOVE
4%(17 LBS/1000 CU FT AIR & >1 MIN;DIZZINESS, IMPAIRED COORDINATION
& REDUCED MENTAL ALERTNESS); ABOVE 5% CONC(22 LBS/1000 CU FT OF
AIR),USE AIR-SUPPLIE D RESPIRATORS.

Exposure Controls

Respiratory Protection:NOT NORMALLY NECESSARY IF PROPER ENGINEERING
CONTROLS ARE IN PLACE. IF PEL/TLV ARE EXCEEDED, USE POSITIVE
PRESSURE AIR-SUPPLIED RESPIRATOR. REVIEW 29CFR1910.134
INSTRUCTIONS/WARNING AS WELL AS NIOSH-R ESPIRATOR DECISON LOGIC
PUB#87.108.
Ventilation:PROVIDE SUFFICIENT GENERAL/LOCAL EXHAUST VENTILATION IN
PATTERN/VOLUME TO CONTROL INHALATION EXPOSURE BELOW PEL/TLV.
Protective Gloves:LINED BUTYL OR AS REQUIRED FOR TASK
Eye Protection:CHEMICAL SPLASH TYPE OR AS REQ.FOR TASK
Other Protective Equipment:AS REQUIRED TO MINIMIZE EXPOSURE & MAXIMIZE
INDIVIDUAL PROTECTION.
Work Hygienic Practices:OBSERVE PROCEDURES SET FORTH BY SAFETY/IH
PERSONNEL FOR USE OF THIS MATERIAL FOR TASK AT HAND
Supplemental Safety and Health
SMALL CONC(5%) OF HALON EXTINGUISH FLAME BY CHEMICALLY INTERRUPTING
COMBUSTION-NOT BY REPLACING O*2. HOWEVER,VAPORIZATION OF EXCESSIVE
AMTS. CAN DEPLETE OR REPLACE O+2 NEEDED FOR BREATHIN THIS INFORMA
TION COPIED FROM A GENERIC MSDS COVERING A FIRE EXTINGUISHER OR TH
SAME MATERIAL.

Chemical Properties

HCC:G3
Boiling Pt:B.P. Text:26F/-3.3C
Melt/Freeze Pt:M.P/F.P Text:-257F/-161C
Vapor Pres:1897 & 70F
Vapor Density:5.7
Spec Gravity:1.83
Evaporation Rate & Reference:RAPID; REFERENCE UNK.
Solubility in Water:NEGLIGIBLE
Appearance and Odor:COLORLESS LIQUIFIED GAS(SEE BOILING PT) W/SLIGHT
ETHEREA ODOR.
Percent Volatiles by Volume:100

Stability

Stability Indicator/Materials to Avoid:YES
ACTIVE METALS (EG. ALKALINE EARTH & ALKALINE EARTH METALS POWDERD AL,
ZN, BE, ETC.) & METAL HYDRIDES.
Stability Condition to Avoid:FLAMES OR HOT SURFACES >900F CAN CAUSE
DECOMPOSITION OF MATERIAL.
Hazardous Decomposition Products:AT HI-TEMPS(>900F : HF, HBR, FREE
BR,POSSIBLE CARBONYL HALIDES, & OXIDES OF BROMING, FLUORING, OR
CARBON.

Disposal

Waste Disposal Methods:COMPLY W/ ALL FEDERAL, STATE & LOCAL
REGULATIONS.RECLAIM MATERIAL IN A SUITABLE VAPOR RECOVERY
SYSTEM/EQUIPMENT.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.