BJFNK - HALON 1301
- MSDS: BJFNK
- Manufacturer: GREAT LAKES CHEMICAL CORP
- Product Name: HALON 1301
- National Stock Number: 1680-00-227-1841
Product Identification
Product ID:HALON 1301
MSDS Date:09/01/1986
FSC:1680
NIIN:00-227-1841
MSDS Number: BJFNK
Responsible Party
WEST LAFAYETTE, IN 47906
US
Emergency Phone: 501-862-5141
Info Phone: 317-463-2511
Cage: 2E394
Contractor
Telephone: 818-359-9317/602-796-1100
Cage: 05167
Ingredients
TRIFLUOROBROMOMETHANE (HALON 1301) (SARA III)
CAS: 75-63-8
RTECS: PA5425000
Fraction By Weight: >/=99.6%
OSHA PEL 1000 PPM
ACGIH TLV: 1000 PPM; 9192
OTHER HALOCARBONS
Fraction By Weight: =0.4%
Hazards
LD50 LC50 Mixture:NONE SPECIFIED BY MANUFACTURER.
Routes of Entry: Inhalation:YES Skin:NO Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:APPROX LETHAL CONC OF HALON 1301 TO
THE RAT IS 80% FOR 15 MINS. HALON 1301 HAS ANESTHETIC & CARDIAC
EFFECTS IN HUMANS AT CONC >10% BY VOL, CONC <10% ARE CONSIDERED
SAFE FOR 0-5 MIN EXPOSURES. HALON 13 01 IS CLASS AS GRP 6 (LEAST
TOXIC) IN THE UNDERWRITERS LABS CLASS OF COMPARATIVE LIFE HAZARDS
OF FIRE EXTING AGENTS.
Explanation of Carcinogenicity:NOT RELEVANT
Effects of Overexposure:THE ANESTHETIC EFFECT OF HALON 1301 AT LEVELS
BELOW 10% IS SIMILAR TO A FEELING OF MILD INTOXICATION. ANESTHETIC
EFFECTS END RAPIDLY AFTER EXPOSURE IS TERMINATED. PROLONGED
EXPOSURE TO CONCENTRATIONS ABOVE 10% (15-20%), MAY LEAD TO
UNCONSCIOUSNESS AND POSSIBLY DEATH.
Medical Cond Aggravated by Exposure:CARDIAC PROBLEMS MAY BE AGGRAVATED
BY OVEREXPOSURE.
First Aid
First Aid:REMOVE VICTIM TO FRESH AIR. GIVE SYMPTOMATIC AND SUPPORTIVE
CARE. GET MEDICAL ATTENTION. NOTE: ADRENALIN IS CONTRAINDICATED IN
THE TREATMENT OF OVEREXPOSURE TO HALON 1301.
Fire Fighting
Flash Point:NON-FLM COMP GAS
Extinguishing Media:HALON 1301 IS A FIRE EXTINGUISHING AGENT
Fire Fighting Procedures:ABOVE 1000F, HALON 1301 MAY RELEASE HYDROGEN
FLUORIDE, HYDROGEN BROMIDE, BROMINE, CARBONYL FLUORIDE AND CARBONYL
BROMIDE
Unusual Fire/Explosion Hazard:PREDOMINANT DECOMPOSITION PRODUCTS ARE
HYDROGEN FLUORIDE & HYDROGEN BROMIDE. THE PRODUCTS ARE IRRITATING &
POTENTIALLY TOXIC IF FIRE EXTINGUISHMENT IS DELAYED.
Accidental Release
Spill Release Procedures:AIR OUT ENCLOSED AREAS IN CASE OF INADVERTENT
DISCHARGE OF HALON 1301.
Neutralizing Agent:NONE SPECIFIED BY MANUFACTURER
Handling
Handling and Storage Precautions:AVOID CONTAINER DAMAGE
Other Precautions:NONE
Exposure Controls
Respiratory Protection:USE NIOSH APPROVED SELF-CONTAINED BREATHING
APPARATUS IF EXPOSED TO CONCENTRATIONS GREATER THAN 10%.
Ventilation:ALL INDOOR AREAS SHOULD BE WELL VENTILATED
Protective Gloves:NONE
Eye Protection:CHEMICAL WORKERS' GOGGLES
Other Protective Equipment:NONE
Work Hygienic Practices:DETERMINE THAT PIPING IS EMPTY BEFORE DOING
MAINTENANCE WORK
Supplemental Safety and Health
NONE SPECIFIED BY MANUFACTURER.
Chemical Properties
HCC:G3
Boiling Pt:B.P. Text:-72F,-58C
Vapor Pres:6200 @ 0C
Solubility in Water:NEGLIGIBLE
Appearance and Odor:ODORLESS, COLORLESS GAS
Stability
Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, FIRES OF METAL HYDRIDES, AND MATERIAL CONTAINING OWN
OXYGEN
Stability Condition to Avoid:NONE
Hazardous Decomposition Products:IN PRESENCE OF FLAMES/HOT SURFACES:
HYDROGEN FLUORIDE, HYDROGEN BROMIDE, BROMINE, CARBONYL FLUORIDE &
CARBONYL BROMIDE
Disposal
Waste Disposal Methods:DISPERSES IN THE ATMOSPHERE
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.