BLZJF - LEAD-ACID CELL (ANTIMONY)

Product Identification

Product ID:LEAD-ACID CELL (ANTIMONY)
MSDS Date:08/05/1988
FSC:6140
NIIN:01-323-1325
MSDS Number: BLZJF

Responsible Party
GNB INC INDUSTRIAL BATTERY DIV WOODLAKE CORP PARK
829 PARKVIEW BOULEVARD
LOMBARD, IL 60148-3249
US

Emergency Phone: 800-424-9300

Info Phone: 708-691-7886

Preparer: JAMES B. DOE, P.E.

Cage: 88219

Contractor
EXIDE TECHNOLOGIES INC CO, GNB INDUSTRIAL POWER DIV
LOMBARD, IL 60148-3249 US

Telephone: 800-872-0471/630-691-7841

Cage: 88219

Ingredients

LEAD (SARA III)

CAS: 7439-92-1

RTECS: OF7525000

Fraction By Weight: 51.4%

OSHA PEL 0.05 MG/M3;1910.1025

ACGIH TLV: 0.15 MG/M3;DUST 9192

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


ANTIMONY (SARA III)

CAS: 7440-36-0

RTECS: CC4025000

Fraction By Weight: 1.0%

OSHA PEL 0.5 MG/M3

ACGIH TLV: 0.5 MG SB/M3; 9192

EPA Report Quantity: 5000 LBS

DOT Report Quantity: 5000 LBS


LEAD PEROXIDE

CAS: 1309-60-0

RTECS: OG0700000

Fraction By Weight: 20.8%


SULFURIC ACID (SARA III)

CAS: 7664-93-9

RTECS: WS5600000

Fraction By Weight: 18.6%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3; 9192

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS

Hazards

Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:ACUTE: NOSE, EYE AND THROAT
IRRITATION. CHRONIC: REPEATED EXPOSURE TO MIST OR LIQUID CAUSES
RESPIRATORY DERMATITIS, CONJUNCTIVITIS AND LACRIMATION.
Explanation of Carcinogenicity:NOT A KNOWN CARCINOGEN.
Effects of Overexposure:STINGING AND BURNING SENSATION TO SKIN AND
EYES.
Medical Cond Aggravated by Exposure:EXPOSURE TO ACID MIST CAN AGGRAVATE
PULMONARY CONDITIONS.

First Aid

First Aid:EYE-IMMEDIATELY WASH WITH LARGE AMOUNTS OF WATER FOR 15
MINUTES. GET MEDICAL ATTENTION. SKIN-WASH SKIN WITH SOAP & WATER.
GET MEDICAL ATTENTION. INHALE-REMOVE TO FRESH AIR. IF BREATHING HAS
STOPPED, G IVE CPR. GET MEDICAL ATTENTION. INGEST-GET MEDICAL
ATTENTION IMMEDIATELY. GIVE LARGE AMOUNTS OF WATER UNTIL MEDICAL
HELP ARRIVES.

Fire Fighting

Extinguishing Media:DRY CHEMICAL.
Fire Fighting Procedures:IN THE EVENT ELECTROLYTE IS EXPOSED DURING A
FIRE, DO NOT COVER OR SPLASH ELECTROLYTE WITH DRY CHEMICAL.
Unusual Fire/Explosion Hazard:CHARGING GENERATES A POTENTIAL EXPLOSION
MIXTURE OF HYDROGEN & OXYGEN GASE IN THE CELL. USE A CELL FLASH
ARRESTOR TO PREVENT INTERNAL CELL EXPLOSION.

Accidental Release

Spill Release Procedures:CONTAIN SPILL WITH ABSORBANT DIKE. APPLY
BAKING SODA, SODA ASH, CAUSTIC SODA OR EQUIVALENT TO NEUTRALIZE THE
ELECTROLYTE.
Neutralizing Agent:SODIUM BICARBONATE, SODA ASH, LIME.

Handling

Handling and Storage Precautions:AVOID ELECTROLYTE CONTACT WITH EYES,
SKIN OR CLOTHING. AVOID BREATHING ELECTROLYTE VAPOR. NO SMOKING
REGULATION IF POSSIBILITY OF HYDROGEN EVOLUTION.
Other Precautions:STORE ELECTROLYTE ONLY IN APPROVED CELLS.

Exposure Controls

Respiratory Protection:SELF-CONTAINED BREATHING APPARATUS IF FUMES OR
MIST ARE PRESENT.
Ventilation:LOCAL EXHAUST TO OUTSIDE AIR OR MECHANICAL EHAUST TO
OUTSIDE AIR.
Protective Gloves:RUBBER GLOVES.
Eye Protection:CHEMICAL SPLASH GOGGLES.
Other Protective Equipment:IMPERVIOUS CLOTHING (I.E. RUBBER APRONS,
BOOTS AND SUITS) ARE RECOMMENDED.
Work Hygienic Practices:WASH HANDS AND PROTECTIVE EQUIPMENT WITH WATER
AFTER USE.
Supplemental Safety and Health
NONE

Chemical Properties

HCC:C1
Appearance and Odor:STRONG ACRID ODOR.

Stability

Stability Indicator/Materials to Avoid:YES
IRON, POWDERED METALS, ZINC AND STEEL REACT WITH SULFURIC ACID AND
RELEASE FLAMMABLE HYDROGEN GAS.
Stability Condition to Avoid:REACTIONS WITH WATER AND ORGANIC
MATERIALS. RUNOFF TO SEWER MAY CREATE FIRE OR EXPLOSION HAZARD. MAY
IGNITE COMBUSTIBLES
Hazardous Decomposition Products:THERMAL DECOMPOSITION INCLUDES HIGHLY
TOXIC FUMES OF SULFURIC OXIDES.

Disposal

Waste Disposal Methods:NEUTRALIZED ELECTROLYTE MAY BE DISPOSED IN SEWER
SYSTEM IF LOCAL REGULATIONS PERMIT. ANY DIKE MATERIAL SHOULD BE
DISPOSED IN ACCORDANCE WITH LOCAL REGULATIONS.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.