BPTZL - NICAD STORAGE BATTERY CELL
- MSDS: BPTZL
- Manufacturer: SAFT AMERICA INC POWER SOURCES DIV
- Product Name: NICAD STORAGE BATTERY CELL
- National Stock Number: 6140-00-460-2905
Product Identification
Product ID:NICAD STORAGE BATTERY CELL
MSDS Date:03/05/1991
FSC:6140
NIIN:00-460-2905
MSDS Number: BPTZL
Responsible Party
VALDOSTA, GA 31603
US
Emergency Phone: 912-247-2331
Info Phone: 912-247-2331
Cage: 09052
Contractor
Telephone: 912-247-2331
Cage: 09052
Ingredients
CADMIUM (SARA III)
CAS: 7440-43-9
RTECS: EU9800000
Fraction By Weight: <13%
OSHA PEL SEE 1910.1027
ACGIH TLV: 0.01 MG/M3 DUST;9394
EPA Report Quantity: 10 LBS
DOT Report Quantity: 10 LBS
CADMIUM HYDROXIDE
CAS: 21041-95-2
Fraction By Weight: <13-16%
OSHA PEL 0.1 MG/M3 (CD FUME)
ACGIH TLV: 0.05 MG/M3 (CD FUME)
NICKEL (SARA III)
CAS: 7440-02-0
RTECS: QR5950000
Fraction By Weight: <30%
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3; 9293
NICKEL HYDROXIDE (SARA III)
CAS: 12054-48-7
RTECS: QR7040000
Fraction By Weight: <30%
OSHA PEL 1 MG NI/M3
ACGIH TLV: 0.1 MG NI/M3; 9293
EPA Report Quantity: 10 LBS
DOT Report Quantity: 10 LBS
POTASSIUM HYDROXIDE (SARA III)
CAS: 1310-58-3
RTECS: TT2100000
Fraction By Weight: 4 - 8%
OSHA PEL C, 2 MG/M3
ACGIH TLV: C 2 MG/M3; 9293
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
COBALT HYDROXIDE'
CAS: 21041-93-0
Fraction By Weight: 0.5%
Hazards
LD50 LC50 Mixture:ORAL RAT LD50 NONE STATED
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:NO
Health Hazards Acute and Chronic:UNDER NORMAL CONDITIONS OF USE, NO
EXPOSURE TO HAZARDOUS COMPONENTS EXISTS. IF INCINERATED, INHALATION
OF FUMES MAY CAUSE RESPIRATORY SYSTEM IRRITATION TO PULMONARY
EDEMA; CHRONIC EXPOSURE MAY CAUSE K IDNEY DYSFUNCTION AND LUNG
INJURY.
Explanation of Carcinogenicity:CADMIUM AND NICKEL ARE REASONABLY
ANTICIPATED TO BE CARCINOGENIC (NTP). NICKEL CARCINOGENIC TO HUMAN
(IARC)
Effects of Overexposure:IF INCINERATED, CHEST PAIN, COUGHING, SWEATING
CHILLS, SHORTNESS OF BREATH AND WEAKNESS.
Medical Cond Aggravated by Exposure:IF INCINERATED, RESPIRATORY SYSTEM
DISORDERS, PROSTATE DISORDERS, LIVER AND KIDNEY DISORDERS.
First Aid
First Aid:IF CONTACT WITH POTASSIUM OR SODIUM HYDROXIDE ELECTROLYTE,
FLUSH WITH WATER FOR 15 MINUTES AND CONTACT PHYSICIAN. IF INHALED,
REMOVE FROM EXPOSURE AND CONTACT PHYSICIAN.
Fire Fighting
Flash Point:NONE
Extinguishing Media:USE EXTINGUISHING MEDIA APPROPRIATE FOR SURROUNDING
FIRE.
Fire Fighting Procedures:FIRE FIGHTERS SHOULD WEAR PROPER PROTECTIVE
EQUIPMENT AND SELF-CONTAINED BREATHING APPARATUS WITH FULL
FACE-PIECE OPERATED IN POSITIVE PRESSURE MODE.
Unusual Fire/Explosion Hazard:TOXIC METAL OXIDE FUMES MAY BE EVOLVED
DURING BURNING.
Accidental Release
Spill Release Procedures:UNDER NORMAL CONDITIONS OF USE, HAZARDOUS
COMPONENTS WILL NOT BE RELEASED. IF POTASSIUM OR SODIUM HYDROXIDE
ELECTROLYTE IS SPILLED, NEUTRALIZED WITH MILD ACID THEN FLUSH WITH
WATER.
Neutralizing Agent:MILD ACID
Handling
Handling and Storage Precautions:DO NOT BREAK OPEN BATTERY CASE; DO NOT
MUTILATE OR SHORT CIRCUIT CASE; DO NOT INCINERATE.
Other Precautions:USE ADEQUATE LOCAL EXHAUST VENTILATION WHEN HANDLING
THE LIQUID IN THE BATTERY, I.E., POTASSIUM HYDROXIDE SOLUTION. IF
CASE IS BROKEN OPEN, ELECTROLYTE IS CORROSIVE ON CONTACT.
Exposure Controls
Respiratory Protection:WEAR NIOSH/MSHA APPROVED SELF-CONTAINED
BREATHING APPARATUS TO PROTECT AGAINST FUMES
Ventilation:GOOD ROOM VENTILATION IS REQUIRED.
Protective Gloves:RUBBER GLOVES
Eye Protection:SAFETY GOGGLES
Other Protective Equipment:IF INVOLVED IN FIRE, FULL PROTECTIVE
CLOTHING.
Work Hygienic Practices:FOLLOWING CONTACT WITH INTERNAL BATTERY
COMPONENTS, WASH HANDS THOROUGHLY BEFORE EATING, DRINKING OR
SMOKING.
Supplemental Safety and Health
NONE GIVEN BY THE MANUFACTURER.
Chemical Properties
HCC:B1
Appearance and Odor:PRISMATIC NYLON CASE WHICH COMPLETELY SEALS THE
COMPONENTS WITHIN.
Stability
Stability Indicator/Materials to Avoid:YES
GENERAL STORAGE PROCEDURES FOR HAZARDOUS MATERIALS ARE ACCEPTABLE.
Stability Condition to Avoid:NONE STATED BY THE MANUFACTURER.
Hazardous Decomposition Products:METAL OXIDE FUMES MAY BE EVOLVED AT
TEMPERATURES ABOVE MELTING POINT.
Disposal
Waste Disposal Methods:CONSULT YOUR LOCAL ENVIRONMENTAL OFFICER. IF
DISCARDED, TREAT AS RCRA HAZARDOUS WASTE. DISPOSE IN ACCORDANCE
WITH FEDERAL, STATE AND LOCAL LAWS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.