BSFMK - AUTOMOTIVE, COMMERCIAL, INDUSTRIAL LEAD ACID BATTERIES

  • MSDS: BSFMK
  • Manufacturer: TROJAN BATTERY CO
  • Product Name: AUTOMOTIVE, COMMERCIAL, INDUSTRIAL LEAD ACID BATTERIES
  • National Stock Number: 6140-01-329-8145
Product Identification

Product ID:AUTOMOTIVE, COMMERCIAL, INDUSTRIAL LEAD ACID BATTERIES
MSDS Date:11/01/1992
FSC:6140
NIIN:01-329-8145
MSDS Number: BSFMK

Responsible Party
TROJAN BATTERY CO
12380 CLARK ST
SANTA FE SPRINGS, CA 90670-3804
US

Emergency Phone: 310-946-8381/800-424-9300(CHEMTREC)

Info Phone: 310-946-8381/714-521-8215

Cage: 94598

Contractor
TROJAN BATTERY CO
SANTA FE SPRINGS, CA 90670 US

Telephone: 562-946 8381 / 800-423-6569

Cage: 94598

Ingredients

SULFURIC ACID (SARA III)-30-38%SULFURIC ACID IN WATER FORMS

CAS: 7664-93-9

RTECS: WS5600000

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3; 9192

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


LEAD (SARA III)-94-97% LEAD ALLOY

CAS: 7439-92-1

RTECS: OF7525000

OSHA PEL 0.05 MG/M3;1910.1025

ACGIH TLV: 0.15 MG/M3;DUST 9192

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


ANTIMONY (SARA III)-LEAD ALLOY CONTAINS 2-6% ANTIMONY

CAS: 7440-36-0

RTECS: CC4025000

OSHA PEL 0.5 MG/M3

ACGIH TLV: 0.5 MG SB/M3; 9192

EPA Report Quantity: 5000 LBS

DOT Report Quantity: 5000 LBS


ARSENIC (SARA III)-0.25% ARSENIC IN LEAD ALLOY

CAS: 7440-38-2

RTECS: CG0525000

OSHA PEL 0.01 MG/M3 (AS)

ACGIH TLV: 0.2 MG/M3; 9192

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


TIN-0.3% TIN IN LEAD ALLOY

CAS: 7440-31-5

RTECS: XP7320000

OSHA PEL 2 MG/M3

ACGIH TLV: 2 MG/M3; 9192

Hazards

LD50 LC50 Mixture:LD50 (ORAL RAT) IS 2140 MG/KG (H2SO4)
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:YES OSHA:YES
Health Hazards Acute and Chronic:SULFURIC ACID:CAUSES SEVERE BURNS TO
ALL TISSUES. INGEST:SEVERE BURNS & ULCERATION. INHAL:SEVERE RESP
IRRIT. LEAD:HAZARD IS FOR INGEST OF DUST IN AIR & ON HANDS WHEN
CLEANING BATTERY POSTS & IF ANY IN TERNAL SOLID MATERIALS ARE
EXPOSED IF BATTERY BREAKS.
Explanation of Carcinogenicity:LEAD AND LEAD COMPOUNDS ARE SUSPECTED
CARCINOGENS BY IARC.
Effects of Overexposure:LEAD COMPOUNDS MAY CAUSE LASSITUDE,WEIGHT
LOSS,CONSTIPATION,ANEMIA,NAUSEA,VOMITING,PARALYSIS,CNS DEPRESSION.
Medical Cond Aggravated by Exposure:SULFURIC ACID MISTS MAY AGGRAVATE
EXISTING RESPIRATORY CONDITIONS.

First Aid

First Aid:SULFURIC ACID:MOST IMPORTANT 1ST AID:IMMED WASH W/LG AMTS OF
RUNNING WATER. REMOVE CONTAMINATED CLOTH UNDER WATER. EYES:WASH
W/WATER LIFTING EYELIDS. REMOVE CONTACT LENSES. INGEST:DO NOT
INDUCE VOMIT. DRINK AS MUCH MILK OR WATER AS POSSIBLEW/O VOMIT. IN
ALL CASES GET MED ATTN IMMEDIATLY. LEAD ALLOY:SKIN:WASH AREA W/SOAP
& WATER. EYE:FLUSH THOROUGHLY W/WATER FOR 15MINS. INGEST:GET MED
ATTN IMMED.

Fire Fighting

Flash Point:NOT FLAMMABLE
Extinguishing Media:SULFURIC ACID & LEAD APPOLY COMPOUNDS ARE NOT
COMBUSTIBLE. USE WATER, CARBON DIOXIDE, DRY CHEMICAL.
Fire Fighting Procedures:WEAR SELF-CONTAINED BREATHING APPARATUS. USE
OF WATER IN EXTINGUISHING BURNING BATTERIES MAY CAUSE SPATTERING
DUE TO THE PRESENCE OF MOLTEN LEAD.
Unusual Fire/Explosion Hazard:AFTER ELECTROLYTE IS ADDED AND BATTERY IS
BEING CHARGED, HYDROGEN GAS IS PRODUCED. BATTERY MAY EXPLODE IF
HYDROGEN GAS TRAPPED INSIDE THE CASE SHOULD IGNITE.

Accidental Release

Spill Release Procedures:USE PROTECTIVE CLOTHING.NEUTRALIZE WITH SODIUM
CARBONATE OR BICARBONATE.COLLECT MATERIAL WITH A NEUTRAL ORGANIC
ABSORBANT(SAND,EARTH);PLACE IN AN APPROPRIATE CONTAINER FOR
DISPOSAL.
Neutralizing Agent:SODIUM BICARBONATE,SODIUM CARBONATE.

Handling

Handling and Storage Precautions:KEEP AWAY FROM SOURCES OF
IGNITION(HYDROGEN IS PRESENT).AVOID SHORTING,IMPROPER CHARGING.
Other Precautions:WHEN BRUSHING BATTERY POSTS,USE PROPER PROTECTIVE
EQUIPMENT(LEAD DUST IS PRESENT).THIS BATTERY SHOULD BE VENTILATED
TO THE OUTSIDE;NEVER VENT IT INTO A SEALED ROOM-HYDROGEN GAS IS
EVOLVED AND IT IS LI GHTER THAN AIR AND DIFFICULT TO DETECT.

Exposure Controls

Respiratory Protection:USE A DUST MASK WHEN BRUSHING BATTERY POSTS.
Ventilation:PROVIDE ADEQUATE VENTILATION.
Protective Gloves:RUBBER GLOVES APPROVED FOR SULFURIC ACID
Eye Protection:CHEMICAL SPLASH GOGGLES AND FACE SHIELD
Other Protective Equipment:EYE WASH STATION AND SAFETY SHOWER.
INDUSTRIAL-TYPE IMPERVIOUS WORK CLOTHING, BOOTS AND APRON AS
REQUIRED.
Work Hygienic Practices:OBSERVE GOOD PERSONAL HYGIENE PRACTICES AND
RECOMMENDED PROCEDURES. LAUNDER CONTAMINATED CLOTHING BEFORE REUSE.
Supplemental Safety and Health
PHYSICAL DATA FOR LEAD ALLOY & CMPDS:SPEC GRAV=9.38 TO 11.34;
NEGLIGIBLE SOLUBITLITY IN WATER; MELTING=620-1630F. THOSE STATED
EARLIER ARE FOR 30-38% SULFURIC ACID IN WATER. THIS SAFETY FILE IS
COMBIN ATION OF BOTH MSDS DTD 21MAR91 & 01NOV92.

Chemical Properties

HCC:C1
Boiling Pt:B.P. Text:230F,110C
Spec Gravity:1.24-1.28
Solubility in Water:COMPLETE
Appearance and Odor:H2SO4:NO COLOR/ODOR LIQ;PB ALLOY:GRAYISHWHITE-DK
BROWN SILVERY SOLID METAL NO O

Stability

Stability Indicator/Materials to Avoid:YES
CONTACT OF ELECTROLYTE WITH ORGANIC MATERIAL
Stability Condition to Avoid:HIGH HEAT,SOURCES OF IGNITION,IMPROPER
CHARGING,SHORT CIRCUITING.
Hazardous Decomposition Products:SULFURIC ACID MIST, SULFUR DIOXIDE AND
CARBON MONOXIDE MAY BE RELEASED WHEN ELECTROLYTE DECOMPOSES.

Disposal

Waste Disposal Methods:BOTH ELECTROLYTE AND SCRAP BATTERIES ARE
REGULATED HAZARDOUS WASTE. SCRAP BATTERIES CONTAIN MATERIALS WHICH
ARE RECYCLABLE AND MUST BE RETURNED TO AUTHORIZED RECYCLER.BROKEN
OR OPENED BATTERIES SHOULD BE PLACED IN A SEALED PLASTIC
CONTAINER.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.