CGMYX - 0630-00002 BATTERY ELECTROLYTE, VARIOUS GRADES
- MSDS: CGMYX
- Manufacturer: TELEDYNE BATTER PRODUCTS TELEDYNE INC COMPANY
- Product Name: 0630-00002 BATTERY ELECTROLYTE, VARIOUS GRADES
- National Stock Number: 6140-01-356-5925
Product Identification
Product ID:0630-00002 BATTERY ELECTROLYTE, VARIOUS GRADES
MSDS Date:02/01/1997
FSC:6140
NIIN:01-356-5925
Kit Part:Y
MSDS Number: CGMYX
Responsible Party
REDLANDS, CA 92373
US
Emergency Phone: 800-535-5053
Info Phone: 714-793-3131
Preparer: ROBIN J. FRIED
Cage: 84375
Contractor
Telephone: 909-793-3131
Cage: 84375
Ingredients
SULFURIC ACID (SARA 302/313) (CERCLA)
CAS: 7664-93-9
RTECS: WS5600000
Fraction By Weight: <50%
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3/3 STEL; 9596
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
Hazards
LD50 LC50 Mixture:NONE SPECIFIED BY MANUFACTURER.
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:YES OSHA:NO
Health Hazards Acute and Chronic:INHAL:CAN CAUSE BURNS OF UPPER RESP
TRACT.LUNG IRRIT & PULM EDEMA MAY OCCUR.SKIN:MAY CAUSE BURNS OR
LOCALIZED IRRIT.EYE:MAY CAUSE IRRIT,CORNEAL BURNS &
CONJUNCTIVITIS.BLINDNESS OR SEVERE OR PERM INJUR Y MAY
RESULT.INGEST:MAY CAUSE BURNS TO MOUTH/ESOPHAGUS/STOMACH.
Explanation of Carcinogenicity:PER MSDS:CARCINOGENICITY:SULFURIC
ACID-IARC.
Effects of Overexposure:ACUTE:MAY CAUSE IRRIT EYES/NOSE/THROAT.DIFFI IN
BREATH MAY BE EXPERIENCED.ACID SPLASH IN EYE/SKIN MAY CAUSE
BURNS/IRRIT.CHRONIC:REP/PROL EXPO TO DILUTE SULFURIC ACID MAY CAUSE
IRRIT TO SKIN.REP/PROL M IST/VAP EXPO OF SULFURIC ACID MAY
CAUSEEROSION OF TEETH,CHRONIC IRRIT EYE,CHRONIC INFLAMM
NOSE/THROAT/BRONCHIAL TUBES.
Medical Cond Aggravated by Exposure:NONE SPECIFIED BY MANUFACTURER.
First Aid
First Aid:EYE:WASH IMMED W/LG AMTS OF H2O LIFT EYELIDS.GET MED
ATTN.SKIN:IMMED FLUSH EXPO AREA W/LG AMTS OF H2O.REMOVE ANY CONTAM
CLOTH.GET MED ATTN.INHAL:REMOVE FROM AREA OF EXPO.BREATH STOP
PERFORM CPR.GET IM MED MED ATN.INGEST:GIVE EMPLOYEE LG AMTS OF H2O
IF CONSC.DONT INDUCE VOMIT.GET MED ATTN.
Fire Fighting
Flash Point:NA
Autoignition Temp:Autoignition Temp Text:NA
Lower Limits:NA
Upper Limits:NA
Extinguishing Media:USE DRY CHEMCIAL OR CO2 EXTINGUIHSER FOR SMALL
FIRE.WATER FOG FOR LARGE FIRES.
Fire Fighting Procedures:NA
Unusual Fire/Explosion Hazard:WHILE BATT IS BEING CHARGED HYDROGEN GAS
IS PRODUCED.BATT MAY EXPLO IF HYDROGEN GAS IS TRAPPED INSIDE BATT
CASE.KEEP IGNITION SOURCES AWAY.
Accidental Release
Spill Release Procedures:ELECTROLYTE SHOULD BE ASBOSRBED W/NON-ORGANIC
TYPE ABSORBENT SUCH AS DRY SAND OR EARTH.AVOID DILUTION WITH WATER.
Neutralizing Agent:USE SODA ASH OR BAKING SODA TO NEUTRALIZE
ELECTROLYTE.
Handling
Handling and Storage Precautions:AVOID USE OF UNINSULATED TOOLS.IF
THEYRE REQUIRE TAKE CARE NOT TO MAKE CONNECTION BETWEEN 2 BATT
TERMINALS AS SEVERE SPARKING MAY OCCUR RESULT IN EXP.
Other Precautions:RINGS/METAL WATCH BANDS SHOULD BE REMOVE WHILE
SERVICING BATT.PROVIDE SUFF VENTI IN ALL WORKAREA-PREVENT BUILDUP
DANGEROUS GASES.BATT RM AIR CONDITIONED AS PART OF OVERALL BLDG SYS
EXHAU AIR FRM BATT RM SHOULDNT RETURN TO AIR DISTRIB(SUPPL)
Exposure Controls
Respiratory Protection:UNDER NORMAL CONDITIONS OF USE RESPIRATORY
PROTECTION IS NOT REQUIRED.HOWEVER SHOULD CONDITIONS ARISE WEHRE
RESPIRATORS ARE NEEDED USE ONLY NIOSH/MSHA RESPIRATORS APPROVED FOR
DUST/FUME/MIST.
Ventilation:BATT CHARGNING AREAS MUST BE ADEQU VENTI TO PREVENT HAZ
CONCN OF FLAMM GAS/ACID MIST.DESIGN CRITERIA FOR VENTI SYS(SUPP)
Protective Gloves:GLOVES APPROV FOR SULFURIC ACID
Eye Protection:CHEM GOGG,FULL FACE SHIELD
Other Protective Equipment:ACID RESISTANT APRON.
Work Hygienic Practices:NONE SPECIFIED BY MANUFACTURER.
Supplemental Safety and Health
VENTI:ARE CONTAIN IN INDUSTRIAL VENTILATION MANUAL PUBLISHED BY ACGIH.
OTHER PRECA:SYS.RM SHOULD HAVE OWN EXHAU SYS CONNNECTED DIRECTLY TO
OUTSIDE AIR.H2/O2 GAS PRODUCED DURING NORMAL BATT OPERATION E SPEC
CHARGING.H2 LIGHTER THAN AIR COLORLESS ODORLESS TASTELESS,DIFFIC TO
DETECT W/O SPEC EQPMT.ASSUME GAS PRESENT,PRECAU
Chemical Properties
HCC:C1
Boiling Pt:B.P. Text:203F,95C
Melt/Freeze Pt:M.P/F.P Text:NA
Decomp Temp:Decomp Text:NP
Vapor Pres:10 @18F
Vapor Density:>1
Spec Gravity:1.22-1.40
pH:NP
Viscosity:NP
Solubility in Water:100%
Appearance and Odor:CLEAR LIQUID.
Percent Volatiles by Volume:NA
Corrosion Rate:NP
Stability
Stability Indicator/Materials to Avoid:YES
CONTACT OF ELECTROLYTE WITH ORGANIC MATERIAL.
Stability Condition to Avoid:NONE
Hazardous Decomposition Products:SULFURIC ACID MIST,SULFUR DIOXIDE AND
CARBON MONOXIDE MAY BE RELEASED WHEN ELECTROLYTE DECOMPOSES.
Disposal
Waste Disposal Methods:ELECTROLYTE SHOULD BE HAULED TO PERMITTED
TREATMENT FACILITY.CHEM SUBJ TO REPORT REQMTS OF SEC 313 TITLE III
SARA/40CFR372.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.