CHZBP - LS 12-100 SEALED,LEAD-CALCIUM BATTERY
- MSDS: CHZBP
- Manufacturer: C AND D CHARTER POWER SYST INC (CAGE REPLACED 0GRM9)
- Product Name: LS 12-100 SEALED,LEAD-CALCIUM BATTERY
- National Stock Number: 6140-01-291-6488
Product Identification
Product ID:LS 12-100 SEALED,LEAD-CALCIUM BATTERY
MSDS Date:04/11/1996
FSC:6140
NIIN:01-291-6488
MSDS Number: CHZBP
Responsible Party
BLUE BELL, PA 19422-0858
US
Emergency Phone: 610-828-9309/800-255-3924
Info Phone: 215-619-2700
Preparer: S.J. KELLY
Cage: 80531
Contractor
Telephone: 406-452-0089
Cage: 06DN1
Ingredients
LEAD (SARA 313) (CERCLA),LEAD COMPOUNDS
CAS: 7439-92-1
RTECS: OF7525000
OSHA PEL SEE 1910.1025
ACGIH TLV: 0.05MG/M3, A3; 9596
EPA Report Quantity: 1 LB
DOT Report Quantity: 1 LB
SULFURIC ACID (SARA 302/313) (CERCLA)
CAS: 7664-93-9
RTECS: WS5600000
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3/3 STEL; 9596
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
TIN
CAS: 7440-31-5
RTECS: XP7320000
OSHA PEL 2 MG/M3
ACGIH TLV: 2 MG/M3; 9596
ALUMINUM (SARA 313)
CAS: 7429-90-5
RTECS: BD0330000
OSHA PEL 15 MG/M3 DUST
ACGIH TLV: 10 MG/M3 DUST; 9596
COPPER (SARA 313) (CERCLA)
CAS: 7440-50-8
RTECS: GL5325000
OSHA PEL 0.1MG/M3 FUME/1 DUST
ACGIH TLV: 0.2 MG/M3 FUME; 9596
EPA Report Quantity: 5000 LBS
DOT Report Quantity: 5000 LBS
WATER
CAS: 7732-18-5
RTECS: ZC0110000
OSHA PEL NOT RELEVANT
ACGIH TLV: NOT RELEVANT
CALCIUM, METAL
CAS: 7440-70-2
RTECS: EV8040000
INERT COMPONENTS
Hazards
LD50 LC50 Mixture:NONE SPECIFIED BY MANUFACTURER.
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:BATTERIES ARE SEALED, RECOMBINANT
DESIGN. UNDER NORMAL USE AND HANDLING CUSTOMER HAS NO CONTACT WITH
INTERNAL COMPONENTS OF BATTERY OR CHEMICAL HAZARDS. UNDER NORMAL
USE AND HANDLING BATTERIES DON'T E MIT REGULATED OR HAZARDOUS
SUBSTANCES. THESE BATTERIES MEET THE DEFINITION OF "ARTICLE" UNDER
29 CFR 1910.1200. ACUTE: TISSUE DESTRUCTION ON CONTACT. MAY CAUSE
2ND/3RD DEGREE BURNS OR BLINDNESS. ING ESTION WILL CAUSE CORROSIVE
BURNS ON CONTACT. MAY BE FATAL IF SWALLOWED. CHRONIC: INHALATION OF
MISTS MAY CAUSE UPPER RESPIRATORY IRRITATION.
Effects of Overexposure:IRRITATION AND BURNING OF EXPOSED TISSUES.
Medical Cond Aggravated by Exposure:RESPIRATORY DISORDERS MAY BE
AGGRAVATED BY PROLONGED INHALATION OF MISTS. TARGET ORGANS: SKIN,
EYES, UPPER RESPIRATORY TRACT.
First Aid
First Aid:SKIN/EYE: FLUSH WITH WATER FOR 15 MINUTES. REMOVE
CONTAMINATED CLOTHING. IF IRRITATION CONTINUES SEEK MEDICAL
ATTENTION. INGESTION: DON'T INDUCE VOMITING. DRINK LARGE QUANTITIES
OF MILK OR WATER. GIVE CPR IF BREATHING HAS STOPPED. SEEK MEDICAL
ATTENTION IMMEDIATELY.
Fire Fighting
Flash Point:NA
Autoignition Temp:Autoignition Temp Text:NP
Lower Limits:NA
Upper Limits:NA
Extinguishing Media:DRY CHEMICAL, HALON, OR CARBON DIOXIDE.
Fire Fighting Procedures:VENTILATE THE AREA WELL. SCBA AND ACID
PROTECTIVE CLOTHING ARE RECOMMENDED.
Unusual Fire/Explosion Hazard:OXYGEN INDEX:>32. HYDROGEN GAS MAY BE
PRESENT. HYDROGEN GAS AND ACID MIST IS GENERATED UPON OVERCHARGE OR
IN FIRES. VENTILATE AREA.
Accidental Release
Spill Release Procedures:BATTERY BROKEN: NEUTRALIZE ANY SPILL
ELECTROLYTE/EXPOSED BATTERY PARTS WITH SODA ASH OR SODIUM
BICARBONATE TIL FIZZING STOPS. PH SHOULD BE NETURAL AT 6-8. WHEN
NEUTRALIZED, SPILL IS NON-HAZARDOUS. KE EP UNTRAINED PEOPLE AWAY
FROM SPILL MATERIAL. PLACE THE BROKEN BATTERY IN A HEAVY GUAGE
PLASTIC BAG OR OTHER NON-METALLIC CONTAINER. PROVIDE ADEQUATE
VENTILATION, HYDROGEN GAS MAY BE (BELOW)
Neutralizing Agent:SODA ASH OR SODIUM BICARBONATE **SPILL CONT: GIVEN
OFF DURING NEUTRALIZATION.
Handling
Handling and Storage Precautions:STORE IN COOL DRY AREA AWAY FROM
COMBUSTIBLES. DONT STORE IN SEALED, UNVENTILATED AREAS. AVOID
OVERHEATING/OVERCHARGING. DO NOT USE ORGANIC SOLVENTS OT OTHER THAN
RECOMMENDED CHEMICAL CLEANERS ON THE BATTERY.
Exposure Controls
Respiratory Protection:NIOSH APPROVED ACID MIST RESPIRATOR IF OSHA PEL
IS EXCEEDED.
Ventilation:GENERAL ROOM VENTILATION SUFFICIENT DURING NORMAL
USE/HANDLING. RECOMMEND 2-3 ROOM AIR CHANGES/HR TO PREVENT BUILDUP
OF HYDROGEN GAS
Protective Gloves:RUBBER OR NEOPRENE
Eye Protection:CHEMICAL GOGGLES/SAFETY GLASSES WITH SIDESHIELD AND FULL
FACESHIELD
Other Protective Equipment:ACID RESIST APRON/CLOTHES. MAINTAIN
EYEWASH,FIRE EXTINGUISHER AND EMERGENCY COMMUNICATION DEVICE IN
WORK AREA.
Work Hygienic Practices:DONT WEAR METALLIC JEWELRY WHEN WORKING WITH
BATTERIES. USE NON-CONDUCTIVE TOOLS ONLY. DISCHARGE STATIC
ELECTRICITY PRIOR TO WORK ON BATTERY.
Supplemental Safety and Health
Chemical Properties
HCC:Z4
Boiling Pt:B.P. Text:NA
Melt/Freeze Pt:M.P/F.P Text:NA
Decomp Temp:Decomp Text:NP
Vapor Pres:NP
Vapor Density:>1
Spec Gravity:1.3 +/-0.010
pH:NP
Viscosity:NP
Evaporation Rate & Reference:NA
Solubility in Water:NA
Appearance and Odor:ACID:COLORLESS OILY FLUID; ACRID ODOR WHEN HOT OR
CHARGING.
Percent Volatiles by Volume:NP
Corrosion Rate:NP
Stability
Stability Indicator/Materials to Avoid:YES
STRONG ALKALINE MATERIALS,CONDUCTIVE
METALS,ORGANIC.SOLVENTS,SPARKS,OPEN FLAME.
Stability Condition to Avoid:OVERHEATING, OVERCHARGING WHICH RESULT IN
ACID MIST/HYDROGEN GENERATION.
Hazardous Decomposition Products:HYDROGEN GAS MAY BE GENERATED IN
OVERCHARGED CONDITION, IN FIRE AT VERY HIGH TEMPERATURES IN FIRE
MAY EMIT CO, CO2, SULFUR OXIDES.
Disposal
Waste Disposal Methods:WASTE#:D002,D008. LEAD AND ITS COMPOUNDS CAN
POSE THREAT IF RELEASED TO ENVIRONMENT. BATTERY IS RECYCLABLE. ITS
ILLEGAL TO DISPOSE OF LEAD-ACID BATTERIES BY ANY MEANS OTHER THAN
RECYCLING. C&D PROVIDE S ENVIRONMENTALLY RESPONSIBLE NATION WIDE
LEAD ACID BATTERY COLLECTION AND RECYCLING PROGRAM. CONTAC T LOCAL
C&D REPRESENTATIVE FOR MORE INFORMATION.
Toxicology
Toxicological Information:BATTERIES ARE SEALED, RECOMBINANT DESIGN.
UNDER NORMAL USE & HANDLING THE CUSTOMER HAS NO CONTACT WITH THE
INTERNAL COMPONENTS OF THE BATTERY OR THE CHEMICAL HAZARDS. UNDER
NORMAL USE & HANDLING THESE BATTERIES DO NOT EMIT REGULATED OR
HAZARDOUS SUBSTANCES. THESE BATTERIES MEET THE DEFINITION OF
"ARTICLE" UNDER 29 CFR 1910.1200 (OSHA HAZARD COMMUNICATION
STANDARD) AND THE SARA COMMUNITY-RIGHT-TO-K NOW REQUIREMENTS.
TOXICOLOGICAL INFORMATION DOES NOT APPLY.
Ecology
Ecological:LEAD AND ITS COMPOUNDS CAN POSE A THREAT IF RELEASED TO THE
ENVIRONMENT.
Transport
Transport Information:ALL DOMESTIC SHIPMENTS: BATTERY, ELECTRIC
STORAGE, WET, NON-SPILLABLE, NOT REGULATED, NO PLACARDS OR LABELS
REQUIRED. FOR WATER EXPORT & CANADIAN SHIPMENTS: UN2800, PROPER
DOT SHIPPING NAME: BATTERIE S, WET, NON-SPILLABLE, ELECTRIC
STORAGE, HAZARD CLASS 8, PACKING GROUP III, LABEL: CORROSIVE (NOT
REQUIRED FOR CANADA).
Regulatory
SARA Title III Information:LEAD, LEAD COMPOUNDS, & SULFURIC ACID ARE
LISTED ON SECTION 313 (40 CFR 372) TOXIC CHEMICALS.
Federal Regulatory Information:SEE 29 CFR 1910.268(B)(2)
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.